Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 7/13/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 7/8/2021
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A code compliant MCP and all the on-site documentation required shall be provided in the machine room. 7/23/2025
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A code compliant MCP and related on-site documentation shall be provided in the machine room. No PM/Callout/Repair/Testing documentation for 2023, 24, 25, 26 REPEAT VIOLATION, still not compliant
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 7/23/2025
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 No No Fire Service Testing must be documented monthly and located in the MCP. No documentation for 2023, 24, 25, 26 REPEAT VIOLATION, still not compliant.
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 No No Fire service testing must be documented monthly. 7/23/2025
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3a No No Machine room door shall be self-closing and self-locking. Door had to be pushed to fully close. Door closer shall be adjusted to close door completely. 7/23/2025
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 No No MCP Fire Service testing must be properly documented monthly on log sheet. There is no log present. 7/13/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.5.7 Record of Oil Usage No No Oil loss log to be updated with each visit. Last entry was in 2020. 7/13/2023
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 7/8/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency alarm bell shall be operational on main and auxiliary power. 12/29/2022
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) Yes No The in car emergency light shall be operational. 12/29/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. 5/21/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes Yes Two-way communication device shall work. Dials, busy signal. Note: This violation was originally cited 5/14/24 and is still not corrected. Elevator Red Tagged for non-compliance. 7/23/2025
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Two-way communication device shall work. Dials, but the signal is busy. 6/20/2025