Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Mist provide Current annual test tag on Mach. room fir Extinguisher. 8.6.1.6.5
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Must preform and document Category 5 full load test. 8.6.1.7.2 2/27/2024
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5 Gland Packing and Seals x Must repair/replace jack packing gland to limit oil leakage. 8.6.5.5 2/27/2024
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.2 Collection of Oil Leakage Must provide means to monitor jack packing gland oil loss. (jack packing overflow tube routed back to pump unit with no means to monitor)
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5 Gland Packing and Seals x Jack seal required to be replaced 3/14/2023
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Pit must be kept free of oil 8.6.4.7
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 Scavenger pump in pit is required to be removed
conversion conversion conversion - reinspect x Governor Rope required to be shorted 7/20/2020
conversion conversion conversion - reinspect x Jack has excessive oil leakage required to be replaced 7/20/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Must post current State operating Cert. in Mach. Room 5.100(2)