Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required. (2nd Notice). This violation must be corrected immediately or the unit may be red tagged out of service per the AHJ.
A17.1-1996 : Elevators 2.17 - Drive machine brake 207.8 x The brake release does not work.
conversion conversion conversion - reinspect x Phase 1 key switch does not recall elevator. Repair. 3/5/2019
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x The elevator hoisting ropes are showing a high degree of wear and shall be replaced. Replace ropes within 30 days of inspection. Reinspection is required. 4/29/2020
A17.1-1996 : Elevators 2.13 - Governor,overspeed switch and seal 1001.2(b)(28) x Governor pull through force is excessive (740) lbs, elevator red tagged until elevator meets manufacturers specifications (125-225 lbs). 1/4/2021
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.1.4(b)(1) Electric Elevators Placed out of Service x x Incomplete 5-yr test. Upon return, test elevator machine brake with 125% rated load and car safety speed. 1/4/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency communication inoperable. Re-inspection required 11/9/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required. 11/5/2024