A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
The elevator hoisting ropes are showing a high degree of wear and shall be replaced. Replace ropes within 30 days of inspection. Reinspection is required.
|
4/29/2020
|
A17.1-1996 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
1001.2(b)(28)
|
x
|
|
Governor pull through force is excessive (740) lbs, elevator red tagged until elevator meets manufacturers specifications (125-225 lbs).
|
1/4/2021
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11.1.4(b)(1) Electric Elevators Placed out of Service
|
x
|
x
|
Incomplete 5-yr test. Upon return, test elevator machine brake with 125% rated load and car safety speed.
|
1/4/2021
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required.
|
11/5/2024
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required. (2nd Notice). This violation must be corrected immediately or the unit may be red tagged out of service per the AHJ.
|
|
A17.1-1996 : Elevators
|
2.17 - Drive machine brake
|
207.8
|
x
|
|
The brake release does not work.
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Phase 1 key switch does not recall elevator. Repair.
|
3/5/2019
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency communication inoperable. Re-inspection required
|
11/9/2023
|