Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 4.2 - Hoistway doors 110 A number of hoistway doors have not had the fire retaining tabs installed on them. Fire retaining tabs are required to keep the hoistway door intact in case of extreme heat conditions. Install fire retaining tabs on all hoistway doors.
conversion conversion conversion - reinspect x Door open button does not work on phase 2 fire services. Also does not work on normal service. Repair 3/5/2019
A17.1-1996 : Elevators 3.27 - Crosshead data plate 1001.2(c)(11) The elevator crosshead data plate has incorrect rope data information. The data plate states the ropes are 3/8” when the actual ropes are 10mm. Correct the information on the data plate and attach to the crosshead.
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x The elevator hoisting ropes are showing a high degree of wear and shall be replaced. Replace ropes within 30 days of inspection. Reinspection is required. 1/5/2021