A17.1-1996 : Elevators
|
3.20 - Governor rope
|
206.5
|
x
|
|
206.5 : Governor rope shall be shortened for proper alignment of tail sheave
|
5/27/2022
|
A17.1-1996 : Elevators
|
3.20 - Governor rope
|
206.5
|
x
|
|
206.5 : Governor rope shall be shortened for proper alignment of tail sheave 2020&2021VIOLATION (2nd REINSPECTION > 6/27/22; 30 days)
|
12/28/2022
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
3.23: Ropes replaced(Jan 2020) no rope data tag .
|
5/27/2022
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
3.23: Ropes replaced(Jan 2020) no rope data tag .
|
5/27/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
B(11)/1.6.1/2.27.1.1.1-3d : 2-way communication device shall work and give proper location (REINSPECTION 14days to REDTAG)
|
12/28/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current state operating certificate in machine room
|
9/25/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
G(1)/A17.1-2016:8.6.1.4 :Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) . (2020&2021 VIOLATION)
|
9/25/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
G(1)Counterweight Hold-down’s are loose and should be adjusted properly.
|
9/25/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
I(6) Repair broken pit light cover. 2020&2021VIOLATION
|
9/25/2024
|
A17.1-1996 : Elevators
|
2.16 -Overhead Beam and Fastenings
|
105.3
|
|
|
isolation pads under machine need replaced
|
9/25/2024
|
A17.1-1996 : Elevators
|
2.16 -Overhead Beam and Fastenings
|
105.3
|
|
|
isolation pads under machine need replaced
|
6/30/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
MCP shall be kept in equipment room, including Fire service testing log, recorded monthly. no MCP / Fire test log on-site
|
9/25/2024
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
needs current certificate posted in machine room
|
9/25/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
Provide current MCP in machine room
|
9/25/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
provide MCP in machine room
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
provide operational phone in cab
|
11/4/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Repair broken pit light cover
|
9/25/2024
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
suspension cables ( red rust or rouge) needs attention-lubrication
|
9/24/2019
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
vacume up red dust in the machine room--NOTE caution on setting off smoke detectors off in machine room
|
9/25/2024
|