Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a needs current certificate posted 9/25/2024
conversion conversion n/a Install metal tags for annual & 5 yr safety test to governor 9/25/2024
A17.1-1996 : Elevators 2.16 -Overhead Beam and Fastenings 105.3 Isolation pads under machine need replaced 9/25/2024
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) vacume up red dust in machine room NOTE caution smoke detectors in the machine room 9/25/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate current certificate needs to be posted in machine room 9/25/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records MCP shall be kept in equipment room, including Fire service testing log, recorded monthly. no MCP / Fire test log on-site 9/25/2024
A17.1-1996 : Elevators 2.16 -Overhead Beam and Fastenings 105.3 Isolation pads under machine need replaced 6/29/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements REPAIR 4TH FLOOR DOOR GUIDES AND UPTHRUST BEARINGS 9/25/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current state operating certificate in machine room 9/25/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) Provide current MCP in machine room 9/25/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) provide onsite MCP
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x provide operational telephone in cab 11/4/2024
A17.1-1996 : Elevators 2.13 - Governor,overspeed switch and seal 1001.2(b)(28) x Install metal tags for annual and 5 yr safety test to governor 6/29/2021
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x 1001.2(c)(29)(4) cables rouging/undersized need replaced 90 days to complete 6/29/2021
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x 3.23: Ropes replaced, no rope data tag 5/27/2022
A17.1-1996 : Elevators 3.20 - Governor rope 1001.2(c)(26) x 206.5 : Governor rope shall be shortened for proper alignment of tail sheave. REINSPECTION >6/27/22 12/28/2022
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x 3.23: Ropes replaced, no rope data tag . 5/27/2022
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x 1001.2(c)(29)(4) cables rouging/undersized need replaced 90 days to complete 6/30/2021
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x suspension ropes (red rust or rouge) need attention--lubricated 9/24/2019