A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
1001.2(c)(29)(4) cables rouging/undersized need replaced 90 days to complete
|
6/30/2021
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
1001.2(c)(29)(4) cables rouging/undersized need replaced 90 days to complete
|
6/29/2021
|
A17.1-1996 : Elevators
|
3.20 - Governor rope
|
1001.2(c)(26)
|
x
|
|
206.5 : Governor rope shall be shortened for proper alignment of tail sheave. REINSPECTION >6/27/22
|
12/28/2022
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
3.23: Ropes replaced, no rope data tag
|
5/27/2022
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
3.23: Ropes replaced, no rope data tag .
|
5/27/2022
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
current certificate needs to be posted in machine room
|
9/25/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current state operating certificate in machine room
|
9/25/2024
|
conversion
|
conversion
|
n/a
|
|
|
Install metal tags for annual & 5 yr safety test to governor
|
9/25/2024
|
A17.1-1996 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
1001.2(b)(28)
|
x
|
|
Install metal tags for annual and 5 yr safety test to governor
|
6/29/2021
|
A17.1-1996 : Elevators
|
2.16 -Overhead Beam and Fastenings
|
105.3
|
|
|
Isolation pads under machine need replaced
|
9/25/2024
|
A17.1-1996 : Elevators
|
2.16 -Overhead Beam and Fastenings
|
105.3
|
|
|
Isolation pads under machine need replaced
|
6/29/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
MCP shall be kept in equipment room, including Fire service testing log, recorded monthly. no MCP / Fire test log on-site
|
9/25/2024
|
conversion
|
conversion
|
n/a
|
|
|
needs current certificate posted
|
9/25/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
Provide current MCP in machine room
|
9/25/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
provide onsite MCP
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
provide operational telephone in cab
|
11/4/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
REPAIR 4TH FLOOR DOOR GUIDES AND UPTHRUST BEARINGS
|
9/25/2024
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
suspension ropes (red rust or rouge) need attention--lubricated
|
9/24/2019
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
vacume up red dust in machine room NOTE caution smoke detectors in the machine room
|
9/25/2024
|