MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Need to clean trash & debris from elevator pit
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Door re-opening device (light ray) still works on Phase I & 11 fire service. Re-inspection required
|
3/6/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone in elevator cab does not work, needs repaired. Re-inspection required
|
3/6/2023
|
A17.1-1996 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
110.10
|
|
|
Bevel ledge at back of hoistway first floor.
|
3/29/2023
|
A17.1-1996 : Elevators
|
4.5 - Access to Hoistway
|
1001.2(d)(5)
|
|
|
Hoistway access pull chain is missing on floor 2.
|
5/3/2023
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate in machine room.
|
5/3/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
5/3/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean trash and debris from pit
|
5/3/2023
|