Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Phone does not call Security. It calls a recording. Please reprogram. 1.6 1/14/2020
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 Yes Yes Car safeties set with full capacity and broke. Red tagged. 8/1/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Clean oil & dirt from elevator car top 12/3/2025
MO Minimum : Elevators (A) - Hoistways (A)13 No No A temporary construction barrier was installed in the elevator hoistway between the elevator cars. This barrier is designed for only temporary use and shall be removed from the hoistway. 12/3/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Clean oil & dirt from elevator car top. 12/3/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. 3/27/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. 3/27/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No There is not “In Case of Fire” signage at each landing as required by the building code. 12/3/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Category 5 incomplete, lower and hold 125%, unintended motion full load down, car and counterweight buffers need smashed, safeties shall be set with 100% capacity, and slide shall be recorded in order to complete category 5 testing. 12/3/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Car top lighting inoperable and shall be repaired, or replaced. 12/3/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Car top light inoperable. Provide means for the car top light to properly function.