Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.1 - Access to machine space 8.10.3.2.2(d) x A 2 hour fire rated machine room door with a self-closing and self-locking door shall be provided. 2/11/2022
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.10.3.2.2(l) x An ABC type fire extinguisher shall be provided. 2/11/2022
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 8.10.3.2.2(h) x Code compliant machine room lighting shall be provided. 2/11/2022
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 8.10.3.2.2(h) x A GFI receptacle shall be provided in the machine room. 2/11/2022
A17.1-2016 : Elevators 2.6 - Ventilation 8.10.3.2.2(k) x Provide proper machine room ventilation. 2/11/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x The fire alarm initiating device at the third landing shall signal the elevator to go into fire service operation. Note: When the device was activated, a building alarm occurred, but the elevator fire service was not initiated. 3/24/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability x Emergency communications loss monitor shall work. 3/26/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation A code compliant MCP and related on-site documentation shall be provided in the machine room. Note: No 2022, and 2023 is blank.
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 4x4 electrical box on cartop needs to have wiring inside box and cover installed.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Pit shall be kept clean. Remove excess debris/oil from pit floor.
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability x Emergency communications loss monitor shall work. - Not corrected at time 3/26/24 re-inspection. 1/14/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 Replace missing 4x4 box cover on side hoistway wall at midway point of hoistway.
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) x The car door restrictor shall be functional.
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability x Emergency communications loss monitor shall work. This violation has not been repaired since previous inspection. This is the final notice for this violation. Failure to correct violation immediately may result in elevator being locked out of service until corrected.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Replace the missing door guide(s).
MO Minimum : Elevators (S) - Fire Service (S)1 x x Install and test all smoke detectors and phases of fire service. 2/11/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x 8.10.3.2.1(d) - Cab flooring shall be installed 3/2/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x 8.10.3.2.2(r) - Disconnects shall be installed at proper NEC specifications 3/2/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x 8.10.3.2.3(m) - All hoistway duct covers and electrical box covers need to be installed. 3/2/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x 8.10.3.2.2(i) - Patch the holes in the machine room walls. 3/2/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x 8.10.3.2.4(b) - Install missing gib on top floor hoistway door. 3/2/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x Car door restrictor shall operate. 3/2/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Firemans' Phase 1 shall operate. 3/2/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x 8.10.3.2.2(d) - A 2 hour fire rated machine room door with a self-closing and self-locking door shall be provided. 3/2/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x 8.10.3.2.2(I) - An ABC type fire extinguisher shall be provided. 3/2/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x 8.10.3.2.2(h) - Code compliant machine room lighting shall be provided. 3/2/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x 8.10.3.2.2(h) - A GFI receptacle shall be provided in the machine room. 3/2/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x 8.10.3.2.2(k) - Provide proper machine room ventilation. 3/2/2023
MO Minimum : Elevators (S) - Fire Service (S)1 x x Install and test all smoke detectors and phases of fire service. 3/2/2023