A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a (Pits and Hoistways)
|
|
|
Clean pit and empty oil recovery bucket.
|
10/15/2020
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide maintenance control program.
|
10/15/2020
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
|
|
Hydraulic jack packings are leaking and need to be replaced
|
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Need to clean hydraulic fluid from elevator pit
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Elevator cab phone repeatedly went to a voicemall. Elevator cab phones shall go to authorized personnel to take appropriate action in case of an emergency. Re-inspection required
|
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work.
|
11/30/2021
|
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspection)
|
x
|
|
Perform OSV testing within 30 days. Re-inspection required
|
7/15/2022
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency two way communication does not work. Phone line shall be monitored 24/7 and be able to provide an accurate location. Repair and reinspect. Code 2.27.1
|
11/4/2025
|