Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone not working. 10/15/2019
A17.1-1996 : Elevators 2.30 - Hydraulic Power Unit 1206.5 The packing head is allowing the car to slowly leak down during the 15 minute standing test. Appears that the packing land is allowing oil to leak back into the tank
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2 way communication not working 4/26/2024
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV does not have a seal. Must be tested on or before next annual inspection date. 9/2/2021
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.1 Examination and Maintenance Need to replace packing on this car
conversion conversion conversion - reinspect x Phone in cab does not work 9/27/2019