| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x |  | emergency phone did not work | 9/22/2025 | 
                
                    | A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 1001.2(b)(11) |  |  | replace the batteries in the battery lowering unit, they are dead | 10/7/2020 | 
                
                    | A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x |  | emergency phone did not work, building is to provide working phone line, tested current phone line no dial tone | 10/12/2022 | 
                
                    | A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x |  | emg lt not working | 10/25/2019 | 
                
                    | A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x |  | emergency phone did not work, phone line was dead | 9/19/2024 | 
                
                    | A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 |  |  | Monthly fire service test log is to be filled out and posted in the machine room | 10/7/2020 | 
                
                    | A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(c)(2) |  |  | The monthly fire service test log is not being filled out monthly | 9/21/2021 | 
                
                    | A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 |  |  | The next weight test on the overspeed valve will be in 2024 | 8/10/2021 | 
                
                    | conversion | conversion | n/a |  |  | emergency lights failed | 12/20/2018 |