MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Phase 1 fire service key switch is broken and shall be repaired. All fire service features shall be tested.
|
2/13/2019
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency alarm bell shall work.
|
2/13/2019
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Emergency light shall work.
|
1/27/2021
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)12 (Door open zones)
|
x
|
|
Existing car door restrictor does not work and shall be repaired and tested.
|
2/13/2019
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
x
|
During Phase 2 fire service, the elevator will not go back to normal operation and is stuck on fire service. Elevator Red Tagged.
|
5/24/2024
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
There is no MCP present.
|
8/28/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
A current ABC type fire extinguisher shall be provided in the machine room.
|
8/28/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Second floor spring closer is missing on hoist door.
|
11/26/2024
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The pit shall be kept clean.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2 On-Site Documentation
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
|
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Holes in hoistway at the 2nd floor shall be repaired.
|
|