MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2 On-Site Documentation No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 9/1/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No A current ABC type fire extinguisher shall be provided in the machine room. 8/28/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 9/1/2026
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Cab lighting - All lamps shall work and be guarded from breakage.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Yes No CAR DOOR SHALL BE RESTRICTED FROM OPENING (more than 4") WHEN OUTSIDE DOOR ZONE
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems No No Car door to return jamb gaps are greater than Code max of 0.5".
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame.
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes Yes During Phase 2 fire service, the elevator will not go back to normal operation and is stuck on fire service. Elevator Red Tagged. 5/24/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency alarm bell shall work. 2/13/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Emergency light shall work. 1/27/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) Yes No Existing car door restrictor does not work and shall be repaired and tested. 2/13/2019
MO Minimum : Elevators (A) - Hoistways (A)13 No No Holes in hoistway at the 2nd floor shall be repaired.
MO Minimum : Elevators (A) - Hoistways (A)13 No No Holes in hoistway at the 2nd floor shall be repaired. 9/1/2026
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No Phase 1 fire service key switch is broken and shall be repaired. All fire service features shall be tested. 2/13/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems No No Replace missing/damaged pickup roller(s) @ floor 1.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No Second floor spring closer is missing on hoist door. 11/26/2024
MO Minimum : Elevators (I) - Pits (I)1 No No The pit shall be kept clean. 9/1/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No There is no MCP present. 8/28/2025
MO Minimum : Elevators (S) - Fire Service 211.8 Switch Keys Yes No When the car is at a landing other than the recall level, with the doors in the normal open position, and, the Phase 2 switch is returned to the ”OFF” position, the car shall recall to the main landing. Currently, went returned to "OFF", the car performs as it it was still "ON".