Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(H) Repair top demarcation light. 1/17/2019
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.1.4 Maintenance Records needs maintenance control program on site and posted on controller unit needs to be cleaned down
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.5 Escalator or Moving Walk Startup Lower right hand side bulstrade has hole worn through Red tagged out of service
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.5 Escalator or Moving Walk Startup Left side balustrade molding bowed out needs to be reattached
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.5 Escalator or Moving Walk Startup Lower machine space cover switch not working
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.14 Escalator Entrance and Egress Ends Balustrade panel gaps on both sides exceeds 5 mm needs correcting
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.2 Escalator Step-to-Skirt Clearance x Lower right hand skirt panel must be flush (broke indexing tool when tested needs step indexing performed to complete test
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.4 Escalator Combplates Upper comb plates 3 plates each missing one tooth
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.4 Escalator Combplates lower right side comb plate has 2 teeth missing adjacent to each other