Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Provide testing of the elevator on emergency power.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.12 - Standby power selection switch 2.27.2 x Provide testing of the elevator emergency power selector switch.
conversion conversion conversion - reinspect x Need to finish inspection. Test gov., car buffer, pullout/pullthrough, car safeties, emergency brake, check hoistway, check car top, FEO, door closing force. 9/23/2019
conversion conversion n/a Machine growling sound. Should be inspected by elevator company. 9/23/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.18 - Traction drive machines 2.24 EXCESSIVE NOISE IN GEAR CASE, should be inspected by elevator company. 12/29/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing x Provide testing of Phase I operation. 4/21/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing x Provide testing of Phase II operation. 4/21/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.12 - Standby power selection switch 2.27.2 x Provide testing of elevator emergency power selector switch. 4/21/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Provide testing of elevator on emergency power. 4/21/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc)(1) Wire ropes shall be replaced x x Wire ropes found to be rouged, undersized and broken lays. Unit removed from service. Replace ropes. 4/21/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Provide full load car buffer test. 4/21/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Provide 125% brake test. 4/21/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Provide full load car safety test, record slide. 4/21/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state elevator certificate. 4/21/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate. 2/6/2024