MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Provide full load car buffer test.
|
4/21/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Provide 125% brake test.
|
4/21/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Provide full load car safety test, record slide.
|
4/21/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.18 - Traction drive machines
|
2.24
|
|
|
EXCESSIVE NOISE IN GEAR CASE, should be inspected by elevator company.
|
12/29/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.12 - Standby power selection switch
|
2.27.2
|
x
|
|
Provide testing of elevator emergency power selector switch.
|
4/21/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Provide testing of elevator on emergency power.
|
4/21/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Provide testing of the elevator on emergency power.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.12 - Standby power selection switch
|
2.27.2
|
x
|
|
Provide testing of the elevator emergency power selector switch.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state elevator certificate.
|
4/21/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
2/6/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)(1) Wire ropes shall be replaced
|
x
|
x
|
Wire ropes found to be rouged, undersized and broken lays. Unit removed from service. Replace ropes.
|
4/21/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
x
|
|
Provide testing of Phase I operation.
|
4/21/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
x
|
|
Provide testing of Phase II operation.
|
4/21/2023
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Need to finish inspection. Test gov., car buffer, pullout/pullthrough, car safeties, emergency brake, check hoistway, check car top, FEO, door closing force.
|
9/23/2019
|
conversion
|
conversion
|
n/a
|
|
|
Machine growling sound. Should be inspected by elevator company.
|
9/23/2019
|