Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)9 Capacity Plate Provide a loading class plate in the car
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)9 Capacity Plate Provide a no passenger plate in car
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)6 Missing loading class plate Missing no passenger signs in car
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Provide loading class plate & no passenger sign in car
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Oil transfer pump in pit has to be removed , a maximum of 5 gallon bucket to replace pump
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Need maintenance control program onsite posted on controller
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance Standing test failed, need to load car with capacity, let stand overnight to see if jack is losing oil/blown jack, unit has been red tagged
MO Minimum : Elevators (I) - Pits (I)1 Remove water from pit
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service and document on log in machine room
MO Minimum : Elevators (S) - Fire Service 211.8 Switch Keys Change Phase 1 & 2 service key switches to match passenger elevator. All fire service keys in the building to be keyed the same
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.15 - sign and operating device symbols 8.11.2.1.1(o) Provide no passenger sign in car 7/20/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.15 - sign and operating device symbols 8.11.2.1.1(o) Provide loading class plate in car 7/20/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits Remove oil from pit floor 7/20/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.3 Guards Between Adjacent Pits Remove oil from pit floor 7/20/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine 7/20/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State certificate in machine room 7/20/2020