MO Minimum : Elevators (S) - Fire Service (S)1 x x The fireman service phase I operation cannot work as required. There are no smoke detectors located at each landing and machine room to initiate phase I fireman service. Smoke detectors need to be installed at each landing and machine room tied into the elevator controller to operate as required. Please note the building is not occupied at this time and has just had major renovations completed, no red tag issued at this time.
MO Minimum : Elevators (H) - Machine Rooms (H)2 In the machine room there is an abandoned water pipe located above the elevator equipment. Remove or mark the pipe as abandoned with orange markings.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Drywall has been removed from the elevator machine room space and shall be reinstalled to maintain the rating of the elevator machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The signage for “In Case of Fire Use Stairs” is not located on all landings.. Install signage that conforms to the building code this elevator was installed to meet.