Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. 2/28/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates A code data plate shall be provided on the machine. 5/22/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher is expired. An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. 5/22/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x In car emergency bell shall work. 6/28/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The in car emergency bell and light shall be operational. 2/12/2020
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean and dry. 5/21/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Top floor door pickup roller shall be replaced. 5/22/2023
MO Minimum : Elevators (I) - Pits (I)1 Water on pit floor shall be removed. The pit shall be kept clean and dry. 5/22/2023