A17.1-2016 : Elevators
|
2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater)
|
8.11.2.1.2(mm)
|
|
|
The seismic device on the counterweight did not initiate when activated. Repair device to operate when activated.
|
10/20/2020
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
The elevator hoisting ropes are showing a high degree of wear and shall be replaced. Replace ropes within 15 days of inspection.
|
6/22/2018
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)6
|
|
|
The gate switch on the elevator car door shall be adjusted so that when the door is in the closed position, the gap between the leading edge of the door and the strike jamb is no more than 2 inches.
|
9/3/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required.
|
8/8/2019
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)3
|
|
|
The top emergency exit has been impeded by electrical conduit added to the car for security cameras and cannot be opened. Remove conduit to allow escape hatch to be opened for maintenance and emergency personnel.
|
10/20/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
A number of floors were missing the fire retaining tabs on the hoistway doors, install fire retaining tabs as required.
|
|