Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems A number of floors were missing the fire retaining tabs on the hoistway doors, install fire retaining tabs as required.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems A number of floors were missing the fire retaining tabs on the hoistway doors, install fire retaining tabs as required.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x A number of floors were missing the fire retaining tabs on the hoistway doors, install fire retaining tabs as required. 7/28/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts A number of floors were missing the fire retaining tabs on the hoistway doors. Need to install tabs
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Elevator cab phone does not work on battery back-up, need to replace phone battery. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Elevator cab phone does not work on battery back-up, need to replace phone battery. Re-inspection required 7/28/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Elevator machine room air conditioner does not work. Repair to keep equipment in correct operating temperature
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.6.4.20.10 x x Elevator traction machine failed to safely lower and hold 125% of the rated load due to brake failure, Elevator red-tagged and removed from service, Need to repair brake system. Re-inspection required before use.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Full load test was never completed last year. Perform the following tests to complete full load test: test drive machine brake with 125% of rated load, car safeties at rated speed with rated load, car buffer test at rated speed with rated load, counterweight buffer test at rated speed, need to test elevator for operation on emergency power, test phase I & II fire service. Re-inspection required 7/28/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to test elevator for operation on emergency power and test phase I & II fire service. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements The car top inspection station does not operate as designed and would not operate properly. The device shall be repaired or replaced to operate as designed. 9/3/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on the elevator at this time. The weight test shall be performed, safeties set, fireman’s service, emergency power, and car buffer compressed before the inspection is completed. 7/9/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)3 The top emergency exit has been impeded by electrical conduit added to the car for security cameras and cannot be opened. Remove conduit to allow escape hatch to be opened for maintenance and emergency personnel. 10/20/2020
A17.1-2016 : Elevators 3.28 - Counterweight and counterweight buffer 8.11.2.1.3(m) There is a top guide roller on the counterweight that has deteriorated and shall be replaced.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri.