Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Existing phone in car not working. Tech determined no power. Repair as needed. 3/15/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone shall be made operable 9/8/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance Piston packing is worn and leaking. Repair as needed.
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency communication/phone is not working. 11/11/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing x Overspeed valve is not sealed and needs full load test 9/8/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x Overspeed valve is not sealed and needs full load test. Re-inspection required 10/30/2024
A17.1-1996 : Elevators 2.32 - Control Valve 1004.2(b)(15) Car failed 15 minute stand test. Determine cause of failure and retest. 11/15/2021
A17.1-1996 : Elevators 2.36 - Hydraulic Cylinders 1004.2(b)(19) Remove scavenger pump from pit and provide code compliant means of oil collection. 11/15/2021
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 OSV is not sealed and must have a cat 5 weight test performed within 90 days or less 10/28/2021
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.2-211.8 x x Hold function failed on Phase II operation. 9/23/2021