MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Existing phone in car not working. Tech determined no power. Repair as needed.
|
3/15/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone shall be made operable
|
9/8/2023
|
A17.1-1996 : Elevators
|
2.32 - Control Valve
|
1004.2(b)(15)
|
|
|
Car failed 15 minute stand test. Determine cause of failure and retest.
|
11/15/2021
|
A17.1-1996 : Elevators
|
2.36 - Hydraulic Cylinders
|
1004.2(b)(19)
|
|
|
Remove scavenger pump from pit and provide code compliant means of oil collection.
|
11/15/2021
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.2-211.8
|
x
|
x
|
Hold function failed on Phase II operation.
|
9/23/2021
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency communication/phone is not working.
|
11/11/2024
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
|
|
OSV is not sealed and must have a cat 5 weight test performed within 90 days or less
|
10/28/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
x
|
|
Overspeed valve is not sealed and needs full load test
|
9/8/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
Overspeed valve is not sealed and needs full load test. Re-inspection required
|
10/30/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
|
|
Piston packing is worn and leaking. Repair as needed.
|
|