Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Incompelte inspection - conduct car buffer/counterweight test, brake and car safety test with rated load at rated speed. 8/19/2021
A17.1-1996 : Elevators 3.20 - Governor rope 1001.2(c)(26) x Governor rope pull through force is at least 850 lbs and governor nameplate is 400 lbs maximum. Repair/replace. 8/19/2021
A17.1-1996 : Elevators 4.8 - Hoistway enclosure 1001.2(d)(8) Hoistway chess at top floor does not work. 5/3/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in machine room. 5/3/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 5/3/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher in machine room is expired, have serviced or replaced 3/6/2024