MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
5/3/2023
|
A17.1-2016 : Elevators
|
3.34 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater)
|
8.6.4.19.17 Earthquake Operation
|
x
|
|
Counterweight seismic displacement device is not working, needs repair
|
3/6/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher in machine room is expired, have serviced or replaced
|
3/6/2024
|
A17.1-1996 : Elevators
|
3.20 - Governor rope
|
1001.2(c)(26)
|
x
|
|
Governor rope pull through force is at least 850 lbs and governor nameplate is 400 lbs maximum. Repair/replace.
|
8/19/2021
|
A17.1-1996 : Elevators
|
4.8 - Hoistway enclosure
|
1001.2(d)(8)
|
|
|
Hoistway chess at top floor does not work.
|
5/3/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Incompelte inspection - conduct car buffer/counterweight test, brake and car safety test with rated load at rated speed.
|
8/19/2021
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate in machine room.
|
5/3/2023
|