Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) No No Remove all non-elevator related materials from the elevator machine room. 9/16/2019
A17.1-1996 : Elevators 1.12 - Car enclosure 1001.2(a)(12) No No Tighten the handrails in the car. 9/16/2019
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No Pit light shall work. 9/16/2019
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 5/25/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 5/25/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No COP shall have car number displayed (multiple units onsite). 10/20/2025
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.2-211.8 Yes Yes Floor selection buttons shall be provided in the car to permit travel to all landings served by the car and they shall be operative at all times when on phase 2 operation. The car calls serving the two entrances which have been bolted shut and walled over shall be removed and a blank cover shall be installed in their place, or access to these entrances shall be restored. - Unit not red tagged. 14 days to comply or unit will be red tagged. 5/3/2021
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.2-211.8 Yes Yes Floor selection buttons shall be provided in the car to permit travel to all landings served by the car and they shall be operative at all times when on Phase 2 operation. The car calls serving the two entrances which have been bolted shut and walled over shall be removed and a blank cover shall be installed in their place, or access to these entrances shall be restored. Unit is locked out and red-tagged. 4/13/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The two-way communication device shall give proper location message. Message identifies the incorrect unit number. 10/20/2025