Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone in elevator cab does not work. 2/5/2019
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)12 x On initial phase I, fire recall at the alternate level, the door open button does not work. Repair 2/5/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Red Tag) x x Phone in elevator cab does not work. 11/19/2019
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide on-site maintenance control program. 4/26/2022
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV installed and not sealed. Perform OSV test on or before next annual inspection. 4/26/2022
A17.1-1996 : Elevators 3.17 - Door and gate equipment 110 Hoistway door closer missing, repair as needed. BOTH FLOORS. 4/19/2022
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x Phase II not working, repair as needed. 15 days to repair and reinspect. 3/1/22 4/28/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone is inoperative. Re-inspection required
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h Fire extinguisher is expired, have serviced or replaced
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Update MCP. Has ‘21 docs, needs ‘22. 4/19/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.1.4(b)(2) Hydraulic elevators Placed out of Service x x Elevator has been decommissioned.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate has expired 5/10/2022