A17.1-2016 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Room and Machinery Space
|
|
|
Perform Annual clean down of Escalator
|
|
A17.1-1996 : Escalators
|
7.10 - Operating and safety devices
|
805.2
|
|
|
Determine where loud squeaking noise is from and correct ASAP
|
|
A17.1-1996 : Escalators
|
7.10 - Operating and safety devices
|
805.2
|
|
|
Isolate vibration, determine cause ,and correct.
|
|
A17.1-1996 : Escalators
|
7.16 - Ceiling intersection guards
|
802.3g
|
|
|
Replace wrong ceiling intersection guards with correct ones.
|
7/2/2020
|
A17.1-1996 : Escalators
|
7.3 - Handrails
|
802.2
|
|
|
Both handrails are cracked. Need to be replaced.
|
7/2/2020
|
A17.1-1996 : Escalators
|
7.3 - Handrails
|
802.2
|
|
|
Replace right side handrail
|
|
A17.1-1996 : Escalators
|
7.5 - Lighting
|
805.7
|
|
|
Top demarcation light fixture failed to illuminate, repair or replacement is required.
|
|
A17.1-1996 : Escalators
|
7.5 - Lighting
|
805.7
|
|
|
Top demarcation light fixture failed to illuminate, repair or replacement is required.
|
|
A17.1-1996 : Escalators
|
7.7 - Combplate and comb step impact device
|
802.6
|
|
|
Replace broken step demarcations.
|
7/2/2020
|
A17.1-1996 : Escalators
|
7.7 - Combplate and comb step impact device
|
1206.6
|
|
|
Comb impact guides are rusted. Pressure test on tripping pressure needed. Reinspect within 30 days.
|
3/29/2023
|
A17.1-1996 : Escalators
|
7.8 - Deck barricades and antislide devices
|
802.3i
|
|
|
Missing deck barricades between the two escalators
|
6/28/2022
|
A17.1-1996 : Escalators
|
7.9 - Steps and upthrust device
|
802.5
|
|
|
Replace broken step demarcation strip.
|
3/29/2023
|
A17.1-1996 : Escalators
|
8.1 - Machinery space access, lighting, receptacle, and condition
|
1206.6a
|
|
|
Clean escalator truss space.
|
3/29/2023
|
A17.1-1996 : Escalators
|
8.1 - Machinery space access, lighting, receptacle, and condition
|
806
|
|
|
The interior top “splash guard” is missing which prevents the accumulation of dirt and debris from entering electrical components. Reinstall splash guard to prevent damage to interior equipment.
|
|
A17.1-1996 : Escalators
|
8.1 - Machinery space access, lighting, receptacle, and condition
|
806
|
|
|
Top interior “splash guard” missing, replace.
|
|
A17.1-1996 : Escalators
|
8.1 - Machinery space access, lighting, receptacle, and condition
|
806
|
|
|
The interior top “splash guard” is missing which prevents the accumulation of dirt and debris from entering electrical components. Reinstall splash guard to prevent damage to interior equipment.
|
|
A17.1-1996 : Escalators
|
8.12 - Steps, step chains, and trusses
|
801.1
|
|
|
Tighten main step chain
|
|
A17.1-1996 : Escalators
|
8.4 - Drive machine and brake
|
804
|
x
|
x
|
Escalator brake torque when tested was at 115lbs, the maximum torque for this unit is 75lbs. Readjust brake torque to be within limits. No red tag issued at this time, reinspection is required.
|
3/4/2024
|
A17.1-2016 : Elevators
|
9.19 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
Record maintenance, call backs, repairs, and testing in MCP and place location of MCP on Controller
|
|
A17.1-2016 : Elevators
|
9.19 - Maintenance Records
|
8.6.1.4.1(d)
|
|
|
Record Step/Skirt Indexing Graph for 2025 in MCP
|
|
conversion
|
conversion
|
n/a
|
|
|
Install top inner deck card
|
1/7/2019
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Comb impact guides are rusted and need to be tested to insure proper impact calibration.
|
2/20/2019
|
conversion
|
conversion
|
n/a
|
|
|
Top left and bottom right end cap weather seal missing.
|
1/7/2019
|
conversion
|
conversion
|
n/a
|
|
|
Repair the bottom demarcation light
|
1/7/2019
|