Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Escalators 7.9 - Steps and upthrust device 802.5 Replace broken step demarcation strip. 3/29/2023
A17.1-1996 : Escalators 8.1 - Machinery space access, lighting, receptacle, and condition 1206.6a Clean escalator truss space. 3/29/2023
A17.1-1996 : Escalators 7.7 - Combplate and comb step impact device 1206.6 Comb impact guides are rusted. Pressure test on tripping pressure needed. Reinspect within 30 days. 3/29/2023
A17.1-1996 : Escalators 7.3 - Handrails 802.2 Both handrails are cracked. Need to be replaced. 7/2/2020
A17.1-1996 : Escalators 7.16 - Ceiling intersection guards 802.3g Replace wrong ceiling intersection guards with correct ones. 7/2/2020
A17.1-1996 : Escalators 7.7 - Combplate and comb step impact device 802.6 Replace broken step demarcations. 7/2/2020
A17.1-1996 : Escalators 7.8 - Deck barricades and antislide devices 802.3i Missing deck barricades between the two escalators 6/28/2022
A17.1-1996 : Escalators 8.4 - Drive machine and brake 804 x x Escalator brake torque when tested was at 115lbs, the maximum torque for this unit is 75lbs. Readjust brake torque to be within limits. No red tag issued at this time, reinspection is required. 3/4/2024
A17.1-1996 : Escalators 7.5 - Lighting 805.7 Top demarcation light fixture failed to illuminate, repair or replacement is required.
A17.1-1996 : Escalators 8.1 - Machinery space access, lighting, receptacle, and condition 806 The interior top “splash guard” is missing which prevents the accumulation of dirt and debris from entering electrical components. Reinstall splash guard to prevent damage to interior equipment.
A17.1-1996 : Escalators 7.5 - Lighting 805.7 Top demarcation light fixture failed to illuminate, repair or replacement is required.
A17.1-1996 : Escalators 8.1 - Machinery space access, lighting, receptacle, and condition 806 The interior top “splash guard” is missing which prevents the accumulation of dirt and debris from entering electrical components. Reinstall splash guard to prevent damage to interior equipment.
A17.1-1996 : Escalators 8.1 - Machinery space access, lighting, receptacle, and condition 806 Top interior “splash guard” missing, replace.
conversion conversion n/a Install top inner deck card 1/7/2019
conversion conversion conversion - reinspect x Comb impact guides are rusted and need to be tested to insure proper impact calibration. 2/20/2019
conversion conversion n/a Top left and bottom right end cap weather seal missing. 1/7/2019
conversion conversion n/a Repair the bottom demarcation light 1/7/2019