Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Repair top and bottom demarcation lights. 1/7/2019
conversion conversion n/a Replace missing outter right deck card and right and left inner deck cards. 1/7/2019
conversion conversion n/a Repair worn safety brake guide 1/7/2019
conversion conversion conversion - reinspect x Comb impact guides are rusted and need to be tested to insure proper impact calibration 2/20/2019
conversion conversion n/a Repair right handrail. Handrail stalling. 1/7/2019
conversion conversion n/a Replace top left and right bottom right end cap weather seal. 1/7/2019
conversion conversion n/a Secure to and bottom nose and impact plate covers. 1/7/2019
A17.1-2016 : Elevators 9.19 - Maintenance Records 8.6.1.4.1(a)(1) Record maintenance, call backs, repairs, and testing in MCP and place sticker on controller where MCP is located
A17.1-1996 : Escalators 8.2 - Stop switch 1008.2b Bottom emergency stop does not buzz when cover is lifted. 7/2/2020
A17.1-1996 : Escalators 8.1 - Machinery space access, lighting, receptacle, and condition 1206.6a Entire unit needs a clean down. 7/2/2020
A17.1-1996 : Escalators 8.1 - Machinery space access, lighting, receptacle, and condition 1206.6a Clean escalator truss space. 3/29/2023
A17.1-1996 : Escalators 7.7 - Combplate and comb step impact device 802.6 Comb impact guides are rusted. Pressure test on tripping pressure needed. Reinspect within 30 days. 3/29/2023
A17.1-1996 : Escalators 7.7 - Combplate and comb step impact device 802.6 Replace broken step demarcations. 7/2/2020
A17.1-2016 : Elevators 7.4 - Entrance and egress ends 8.6.8.14 Bottom landing floor plate is peeling up causing a trip hazard 7/21/2023
A17.1-2016 : Elevators 7.19 - Maintenance records 8.6.1.4.1(d) Record printed Graph of Step/Skirt Indexing for 2025 in MCP
A17.1-2016 : Elevators 7.17 - Step/skirt clearances, panels, and performance index 8.6.8.3.3 Step/Skirt indexing clearances failed on both sides exceeding the allowed amount of .25 7/21/2023
A17.1-1996 : Escalators 7.17 - Step/skirt clearances, panels, and performance index 1206.6c Step indexing over limit. Repair and Reinspect. 3/29/2023
A17.1-2016 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Room and Machinery Space Provide annual clean down of escalator truss, top and bottom end
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Step has broken yellow demarcation strip. 11 CSR 40-.065 T 8.6.11.6.2(i) 7/21/2023