Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. 7/14/2021
A17.1-2016 : Elevators 3.23 - Suspension Means 8.11.2.1.3(cc) replace hoist ropes, they are rouged and under size. 2nd year notice 7/14/2021
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Emergency lights didn’t come on, replace battery 11/4/2024
A17.1-1996 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 1002.3a x x did no perform any of the 5 year inspection and test in Rule 1002.3. reinspect and perform all of the 5 year tests in 1002.3
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x replace hoist ropes, guage goes all the way on at the 7th floor on the counterweight side 3/29/2021