Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 1002.3a x x did no perform any of the 5 year inspection and test in Rule 1002.3. reinspect and perform all of the 5 year tests in 1002.3
A17.1-1996 : Elevators 3.28 - Counterweight and counterweight buffer 202 counterweight is compressing the buffer when the car is at the top landing, remove the stingers from the counterweight frame 10/26/2023
A17.1-1996 : Elevators 2.17 - Drive machine brake 207.8 x Brake failed to lower stop and hold 125% of rated load 9/14/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. 7/14/2021