| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate |  |  | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. | 7/14/2021 | 
                
                    | A17.1-1996 : Elevators | 5.10 - Compensating chains, ropes, and sheaves | 1001.2(e)(8) | x |  | Comp ropes need to be shortened, they are dragging the pit floor | 2/26/2025 | 
                
                    | A17.1-1996 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 1002.3a | x | x | did no perform any of the 5 year inspection and test in Rule 1002.3. reinspect and perform all of the 5 year tests in 1002.3 | 5/15/2025 | 
                
                    | A17.1-1996 : Elevators | 2.13 - Governor,overspeed switch and seal | 206 | x | x | the pull thru is not in the range marked on the governor minium of 112 and Maximum of 225, measured 74 | 10/1/2020 |