A17.1-1996 : Elevators
|
5.10 - Compensating chains, ropes, and sheaves
|
1001.2(e)(8)
|
x
|
|
Comp ropes need to be shortened, they are dragging the pit floor
|
2/26/2025
|
A17.1-1996 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
206
|
x
|
x
|
the pull thru is not in the range marked on the governor minium of 112 and Maximum of 225, measured 74
|
10/1/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year.
|
7/14/2021
|