Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an unsealed overspeed valve. A category 5 test shall be performed on this unit on or before the next annual inspection.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State operating certificate in machine room.
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h Provide current tested fire extinguisher in machine room.
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 Where additional power sources is connected to load side of disconnect, it shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is opened. (Confirm operation and correct if needed).
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Up-to-date operating certificate required in the machine room.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) The pit shall be kept clean.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
conversion conversion conversion - reinspect x In car emergency telephone shall work. 5/21/2018
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Remove the oil & water from the pit. The pit shall be kept clean and dry. 3/1/2021
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x The auxiliary battery lowering shall be operational. 11/16/2022
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x Machine room smoke detectors shall be operational. Smoke detector is currently covered and preventing it from being operational. 9/27/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. 9/27/2023
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 x Where additional power sources is connected to load side of disconnect, it shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is opened. 9/27/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. 6/12/2024
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 x Where additional power sources is connected to load side of disconnect, it shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is opened. 6/12/2024