A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5a Lighting
|
|
|
Machine room lighting shall properly operate.
|
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5a Lighting
|
|
|
Machine room lights shall work.
|
|
conversion
|
conversion
|
n/a
|
|
|
Pit light shall work.
|
4/18/2019
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State operating certificate in machine room.
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
|
|
Provide current tested fire extinguisher in machine room.
|
|
conversion
|
conversion
|
n/a
|
|
|
Replace damaged fire service signage in car.
|
4/18/2019
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
1001.2(a)(17)
|
x
|
|
The auxiliary battery lowering shall be operational.
|
11/16/2022
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test.
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Up-to-date operating certificate required in the machine room.
|
|
A17.1-1996 : Elevators
|
2.11 - Disconnecting Means and Control
|
210.4
|
x
|
|
Where additional power source is connected to load side of disconnect, it shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is opened.
|
|
A17.1-1996 : Elevators
|
2.11 - Disconnecting Means and Control
|
210.4
|
x
|
|
Where additional power source is connected to load side of disconnect, it shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is opened.
|
9/27/2023
|
A17.1-1996 : Elevators
|
2.11 - Disconnecting Means and Control
|
1001.2(b)(11)
|
|
|
Where additional power source is connected to load side of disconnect, it shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is opened. (Confirm operation and correct if needed)
|
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
x
|
|
Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3.
|
9/27/2023
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
x
|
|
Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3.
|
|