Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 1001.2(b)(11) Where additional power source is connected to load side of disconnect, it shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is opened. (Confirm operation and correct if needed) 3/24/2025
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x The auxiliary battery lowering shall be operational. 11/16/2022
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 3/24/2025
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. 9/27/2023
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 x Where additional power source is connected to load side of the disconnect, it shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is open. 9/27/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certificate in machine room. 3/24/2025
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h Provide a current tested Fire Extinguisher in machine room. 3/31/2025
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting Machine room lighting shall properly operate. 3/24/2025
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 Pit lighting shall be operational. 3/31/2025
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Up-to-date operating certificate is required in the machine room. 3/24/2025
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting Machine room lights shall work. 3/17/2025
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 x Auxiliary battery lowering worked, but appeared that auxiliary contacts have not been installed. Where additional power source is connected to load side of the disconnect, it shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is open. 6/12/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Pit light shall work. 3/24/2025
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Battery lowering does not work. Battery lowering shall be operational and the disconnect shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is open. 2/13/2025
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be obtained and displayed in the machine room. 3/24/2025
A17.1-1996 : Elevators 1.17 - Standby power operation 207.8 x Battery lowering does not work or have batteries. Battery lowering shall be operational and the disconnect shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is open. Note: This is the final notice for this violation. Failure to correct the violation will result in the elevator being red tagged and locked out of service.
conversion conversion n/a Replace damaged fire service signage in car. 4/18/2019