Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. 10/26/2018
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Cab ceiling is open egg-crate type, which does not provide protection should bulbs shatter. Lights should be guarded by plastic tubes or other manner to provide protection. 10/7/2020
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Maintenance control program shall include written procedures for tests and inspections on site. 10/7/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 12/30/2024
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Fire service testing must be documented monthly. The form is present in the MCP, but is blank.
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Stop switch not over ridden during fire service 11/20/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2-way communication device shall work. Microphone is not working.