Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.18 - Traction drive machines 8.11.2.1.2(p) x Controller is indicating 125% load when car is loaded at capacity. 1/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.19 - Gears, bearings, and flexible couplings 8.11.2.1.2(q) Determine condition of hoist machine bearings and gears. Machine is making loud noise when running down with capacity load. 1/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall be operational. 2/1/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) x Phase 2 fire service not operating properly. 2/1/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.14 - Code data plate 8.7.1.8 Provide a code compliant code data tag. 1/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide code compliant maintenance control program documents. 1/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) x The door open button in the firefighters phase two panel is intermittently sticking in the actuated position and shall be repaired or replaced. 4/3/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 8.11.2.1.5(j) x x The following items still need to be tested for completion of Category 5 Test: Set the car safeties, test ascending car over speed, and confirm proper operation of load weighing device. 11/18/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x The in-car emergency lights shall be operational. 4/3/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.19 - Gears, bearings, and flexible couplings 8.6.1.6.2 Verify the oil level in the hoist machine. 1/10/2020