A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
|
|
mcp not being maintained
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
no current cirt. posted
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
wiring not pertaing to elev hanging dn below celing
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door not self closing or self locking
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
no current. cirt. displayed
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
debris on machroom floor
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
materials not necessary for the maint of the elev. shall not be stored in machroom
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
phone was answered but security couldnt tell me my location
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
pit has about 18 inches of standind water in it. Red Tagged
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
door key for machine room dosnt work the lock
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
no cirt. of operation displayed
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
emg phone not working
|
4/14/2022
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
phone not working
|
10/13/2022
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
fire int.devices in mach room not working bypassed
|
10/13/2022
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.2-211.8
|
x
|
x
|
machroom is at designated level smoke det. in mach room dosnt send car to alternate level as it should. 2.11.3b(2)
|
11/30/2022
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
phone not working
|
3/20/2023
|