Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)8 No No wiring not pertaing to elev hanging dn below celing
MO Minimum : Elevators (I) - Pits (I)1 No No pit has about 18 inches of standind water in it. Red Tagged
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No no current. cirt. displayed
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No no current cirt. posted
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No no cirt. of operation displayed
MO Minimum : Elevators (I) - Pits (I)1 No No needs to be cleaned an sump cover put back on
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No materials not necessary for the maint of the elev. shall not be stored in machroom
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door not self closing or self locking
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Mach room floor dirty
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No door key for machine room dosnt work the lock
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No debris on machroom floor
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation No No mcp not being maintained
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No phone was answered but security couldnt tell me my location 2/4/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No phone not working 10/13/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No phone not working 3/20/2023
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device Yes Yes fire int.devices in mach room not working bypassed 10/13/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No emg phone not working 4/14/2022
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.2-211.8 Yes Yes machroom is at designated level smoke det. in mach room dosnt send car to alternate level as it should. 2.11.3b(2) 11/30/2022