A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
All the on site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
|
3/16/2022
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
3/16/2022
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test.
|
3/16/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
This unit is not equipped to run on emergency power, but has an emergency power selector switch. The switch shall be removed.
|
3/16/2022
|
A17.1-1996 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
102.1
|
|
|
The temporary jumper in the controller shall be removed or made permanent if a motor thermal overload has not been provided. This temporary jumper is marked for "pump motor thermal overload". The elevator has a working motor overload in the solid state starter.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
The pump motor belts are cracked and shall be replaced and adjusted so they will not slip under load.
|
|
A17.1-1996 : Elevators
|
3.3 - Top-of-car operating device
|
210.1d
|
|
|
The machine room inspection switch on the main board is shorted in the up direction and shall be repaired or replaced.
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.7 Firefighter' Service Operating Procedures
|
|
|
Firefighters phase one instructions shall be posted near the phase one key switch in the hallway at the egress floor.
|
|