Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/16/2022
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures No No Firefighters phase one instructions shall be posted near the phase one key switch in the hallway at the egress floor. 11/21/2025
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No All the on site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 3/16/2022
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. 3/16/2022
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) Yes No The emergency lowering device (ERU) shall be operational. 5/6/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No This unit is not equipped to run on emergency power, but has an emergency power selector switch. The switch shall be removed. 3/16/2022