Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 2.16.8 Yes No 125% brake test failed. Red tagged. 7/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Emergency generator shall be tested to ensure that the elevators will run on emergency power. Re-inspection required 8/8/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No This elevator is equppied with a backup generator, and shall be tested for operation on emergency power. 4/20/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No This elevator is equipped with a backup generator, and shall be tested for operation on emergency power. The electric company never showed up to perform test
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Phone inoperative. Repair 5/17/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Provide on-site records for maintenance control program. 2/8/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 No No Lobby warning placards on 4th and 5th floor are missing. 2/8/2021
conversion conversion n/a No No Repair emergency light in car 7/9/2020
conversion conversion n/a No No Make Selsmic Feature Operational 7/9/2020