Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) A copy of the MCP shall be kept in the machine room for each elevator 2/23/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current copy of the state operating certificate shall be displayed in machine room 2/23/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Alarm bell inoperable during auxiliary power,and shall be repaired or replaced. 2/23/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.3 Provide Auxiliary Lighting x Auxiliary lighting inoperable and shall be repaired or replaced. 3/27/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.3 Provide Auxiliary Lighting x Auxiliary lighting inoperable, repair or replace as needed. 2/23/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.1 Not less than two lamps Can lighting only has one operating bulb. Repair or replace to ensure all can lighting is operable. 2/23/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Fire extinguisher in machine room is expired. Replace or have serviced. 2/23/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Hoistway access pull chain on the top landing shall be repaired or replaced. 2/23/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Hoistway access pull chain on the top landing shall be repaired or replaced. 2/23/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.1 Not less than two lamps One light fixture failed to operate on the day of testing, repair light fixture. 2/23/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) x Phase 2 operation failed, reinspection required. 2/23/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.11.2.1.4(e) Replace missing chains on freight door access on 2nd & 3rd floors to access top of elevator. 9/15/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.11.2.1.4(e) Replace missing pull chains on freight door access on 2nd & 3rd floors to access top of elevator 2/23/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 2.12.6 Replace missing pull chains on freight door access on 3rd floor to access top of elevator 2/23/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.8 - Top emergency exit 2.14.1.5 The car top escape hatch shall be secured closed and shall be openable without the use of special tools. 2/23/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 2.14.7 The car top inspection light/fixture did not operate. Repair light/fixture for proper operation and illumination for maintenance/emergency personnel. 2/23/2026