A17.1-1996 : Elevators
|
2.3 - Housekeeping
|
n/a
|
|
|
Remove all the debris from the pit floor
|
1/9/2020
|
A17.1-1996 : Elevators
|
3.10 - Hoistway construction
|
100
|
|
|
Stop the leak around the vent at the top of the hoistway and replace the drywall back to a 1 hour rated assemble.
|
2/10/2021
|
A17.1-1996 : Elevators
|
3.10 - Hoistway construction
|
1001.2(c)(16)
|
|
|
Repair the drywall around the vent at the top of the hoistway and fire caulk around the vent to provide for a 1 hour rated assembly.
|
4/29/2019
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Empty the water from the pit
|
4/29/2019
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Replace the non working sump pump, I suggest adding a second pump as this is an ongoing problem here.
|
4/29/2019
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Replace the non working pit light as it has been under water. NEC requires that all the wiring that is subject to a wet location is to be NEMA 4 rated water proof equipment.
|
4/29/2019
|