Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Empty the water from the pit 4/29/2019
A17.1-1996 : Elevators 2.3 - Housekeeping n/a Remove all the debris from the pit floor 1/9/2020
A17.1-1996 : Elevators 3.10 - Hoistway construction 1001.2(c)(16) Repair the drywall around the vent at the top of the hoistway and fire caulk around the vent to provide for a 1 hour rated assembly. 4/29/2019
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Replace the non working pit light as it has been under water. NEC requires that all the wiring that is subject to a wet location is to be NEMA 4 rated water proof equipment. 4/29/2019
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Replace the non working sump pump, I suggest adding a second pump as this is an ongoing problem here. 4/29/2019
A17.1-1996 : Elevators 3.10 - Hoistway construction 100 Stop the leak around the vent at the top of the hoistway and replace the drywall back to a 1 hour rated assemble. 2/10/2021